SIEMENS LAE10 110V FLAME SAFEGUARDS FOR BURNER

$599.00

Availability: In Stock
Brand:SEIMENS

Description

The Siemens LAE10 110V is a plug-in flame safeguard relay designed for monitoring oil burners with intermittent operation, specifically using RAR7/RAR8 selenium photocell detectors. It ensures safe combustion by supervising ignition and main flames in industrial boilers and heating systems, featuring automatic light simulation testing for safety.

Key Features and Technical Description
  • Application: Ideal for forced draft oil burners, industrial furnaces, and systems requiring dual flame monitoring (using multiple units).
  • Flame Monitoring: Uses selenium photocell detectors (RAR…) to detect oil flames.
  • Voltage: While commonly 220-240V, 110 V AC versions are available.
  • Design: A compact plug-in design simplifies installation and service. It consists of a power supply, flame signal amplifier, flame relay, and auxiliary relay.
  • Safety Features: Automatic light simulation test (safety check during startup/purge) ensures the flame detector does not show a false flame signal.
  • Durability: Designed for approx. 250,000 burner startup cycles (roughly 10 years of usage) under normal conditions.
  • Protection Class: IP40, with a working temperature range of \(-20^{\circ }\text{C}\) to \(+60^{\circ }\text{C}\)